The Texas Data Center Playbook
By: Julia Chialastri

State directives ordering a comprehensive audit of Texas data center grid interconnections, occurring alongside subsequent freezes on Texas Commission on Environmental Quality (TCEQ) environmental and water permits, have temporarily paused new data center developments, giving city and county leaders a crucial window to establish local oversight standards.[1] [2] With Texas Governor-elect Gina Hinojosa now pledging to implement a complete moratorium on new data center approvals and construction, the regulatory process has become even more uncertain.[3] Together, these delays give city and county leaders a crucial window to establish local oversight standards. While data centers bring tax revenue and critical digital infrastructure, rapid growth has fueled public friction over water usage, grid capacity, and residential utility rates.[4] [5] [6] [7]
This divide often originates with developer choices: speculative developers may lower their upfront capital expenditures (CapEx) by installing lower-cost, high-consumption evaporative cooling strategies that draw heavily on host municipal water supplies, whereas community stewards invest in advanced closed-loop cooling and microgrids to minimize local resource strain. [8] [9] Evaluating incoming projects requires local decisionmakers to look beyond surface-level power and water draw to assess the trade-offs between energy efficiency, water consumption, and long-term facility design. This brief introduces industry-standard efficiency metrics, suggests potential regional deployment models tailored to Texas microclimates, and presents a checklist of local permitting considerations.
Defining Water and Energy Efficiency in Data Centers
Evaluating data center efficiency requires clear, standardized metrics. While several exist, the ISO/IEC 30134 standard family relies on two core metrics developed by The Green Grid: Power Usage Effectiveness (PUE) and Water Usage Effectiveness (WUE).[1] [2] Because PUE and WUE are widely adopted, standardized under ISO guidelines, and routinely reported, this brief focuses on both.
1.1. Power Usage Effectiveness (PUE)
PUE measures overall facility energy efficiency by comparing total power consumed to energy delivered to computing hardware:

An ideal PUE is , indicating that zero supplemental energy is lost to cooling, lighting, or power distribution.[1] Regulatory baselines are tightening globally: the U.S. Federal Government mandates a maximum PUE of for its federal data centers, while international standards, such as Germany's Energy Efficiency Act, require new facilities to achieve a PUE of 1.2 or lower. [2] [3]
1.2. Water Usage Effectiveness (WUE)
The companion metric to PUE is Water Usage Effectiveness, which measures annual on-site water consumption relative to IT energy output:

The theoretical ideal WUE is , when on-site water consumption is zero. [1] As of August 2026, the U.S. does not mandate a maximum WUE threshold or require public reporting under ISO/IEC 30134-9. [2] In contrast, the European Union's Energy Efficiency Directive (EED) mandates WUE reporting under ISO standards and emphasizes monitoring freshwater inputs to safeguard local drinking supplies. [3] [4]
1.3 PUE and WUE Consideration: Direct vs. Indirect Resource Footprints
Evaluating a facility of a true environmental footprint requires accounting for both direct (on site) and indirect (off site) resource usage. [1] On-site water and electricity is used for cooling towers, adiabatic systems, lighting and IT hardware operations.[2] Conversely, off site consumption of water and energy consumption largely takes the form of the regional power generation plants that provide electricity. Because power generation relies heavily on cooling, every kilowatt-hour drawn from the grid carries an embedded water footprint.[3] Consequently, operational choices designed to eliminate direct on-site water use via power-intensive air cooling can backfire. By increasing total facility power demand, dry cooling simply shifts the water burden upstream, increasing indirect water consumption across regional power plants and the broader watershed. [4]
Example Regional Deployment Models
Texas encompasses vastly different microclimates, water tables, and grid dynamics, a Good Steward approach must be tailored to regional realities.[1] The scenarios and solutions created below are fictional and should not be taken as an authoritative guide to what cooling solution should be selected for a particular Texas region. They are included to help illustrate how industry efficiency metrics and regional needs combinations can produce different ideal solutions.
A. Scenario A Water-Strained: West Texas and Panhandle (Permian Basin / High Plains)
Operational Challenges: Severe groundwater scarcity, protection of fragile regional aquifers (e.g., Ogallala), low relative humidity, and municipal or groundwater conservation district limits.[1]
One Good Steward Strategy: Deploying higher CapEx closed-loop D2C or single/two-phase dielectric immersion cooling paired with dry air coolers. This recirculates a fixed volume of fluid, minimizing municipal water consumption.[2]
Community Connection: Protects local drinking and agricultural water supplies, reduces municipal permitting friction, and aligns with state water conservation goals.[3]
B. Scenario B Energy Strained: The Triangle (DFW, Austin, San Antonio)
Operational Challenges: High urban server density combined with extreme summer heatwaves (multiple days with excessive heat) that can lead to high peak power prices, paired with accessible municipal water utility infrastructure.
One Good Steward Strategy: Utilizing hybrid evaporative/adiabatic cooling integrated with Thermal Energy Storage (TES). The facility chills water during off-peak night hours and uses it during hot afternoon peaks, relieving stress on the local grid. [1] [2]
Community Connection: Helps prevent localized grid overload during peak summer periods but requires water management agreements with local municipal utilities.[3]
C. Scenario C High-Density AI Infrastructure: Industrial Corridors and Coastal Texas (East Texas / Gulf Coast)
Operational Challenges: Ultra-high-density AI processing clusters generating concentrated heat; high ambient humidity limits traditional evaporative cooling efficiency; proximity to industrial water infrastructure or reclaimed non-potable water sources.[1]
One Good Steward Strategy: Utilizing Direct-to-Chip cooling coupled with industrial non-potable or reclaimed wastewater loops, preserving municipal drinking water for residents.[2]
Community Connection: Preserves municipal drinking water supplies while enabling high-value computational infrastructure in industrial corridors.[3]
From Metrics to Oversight: Permitting Considerations
To translate these regional cooling realities into enforceable municipal oversight, local planning commissions, city councils, and county commissioners should evaluate:
Ultimate Entity Disclosure: Full organizational hierarchy identifying the Ultimate Parent Entity (UPE) behind applicant LLCs.
State Audit Clearance: Verification that the project has completed required PUCT/ERCOT data center grid audit clearances.
PUE/WUE Performance Baselines: Require PUE and WUE targets linked to site-appropriate cooling technology.
On-Site Power Mitigation: Detailed plans for microgrids, fuel cells, or battery storage to shield residential utility rates during peak demand.
Net-Benefit Economic Audit: Independent ROI analysis weighing requested tax abatements against long-term water, grid, and public infrastructure costs.
Decommissioning Guarantees: Binding site-restoration bonds preventing stranded industrial assets in the event of hardware obsolescence.
Conclusion:
Texas encompasses diverse microclimates, distinct water tables, and varying grid constraints, no single cooling strategy or blanket legislative mandate can serve as a universal solution. Optimal data center design requires balancing local water availability, regional grid stability, and thermal efficiency. To foster sustainable growth, city and county officials should consider requiring reporting on projected Power Usage Effectiveness (PUE) and Water Usage Effectiveness (WUE) metrics, while operators must commit the necessary capital expenditure to align facility cooling with long-term regional resource limits. By pairing tailored cooling architectures with transparent community engagement, operators can protect vital municipal water supplies and grid reliability while shielding their own projects from regulatory delays, punitive utility fees, and operational downtime.
Bibliography:
Akin Gump Strauss Hauer & Feld LLP. "Texas Pauses Data Center Interconnections and Environmental Permits Pending Statewide Audit." Insights & Legal Alerts, August 7, 2026 (updated September 2026). https://www.akingump.com/en/insights/alerts/texas-pauses-data-center-interconnections-pending-statewide-audit.
ASHRAE Technical Committee 9.9. AI Data Center Energy Performance & Thermal Framework. Atlanta: ASHRAE, 2024.
ASHRAE Technical Committee. Liquid Cooling Guidelines for Datacom Equipment Centers. 2nd ed. Atlanta: ASHRAE, 2014.
ASHRAE Technical Committee. Thermal Guidelines for Data Processing Environments. 5th ed. Atlanta: ASHRAE, 2021.
Chidolue, Onyinyechukwu, et al. "Green Data Centers: Sustainable Practices for Energy-Efficient IT Infrastructure." Engineering Science & Technology Journal 5, no. 1 (January 2024): 99–114. https://doi.org/10.51594/estj.v5i1.730.
Congressional Research Service. Data Centers and Water: Frequently Asked Questions. CRS Report R49057. Washington, DC: Congressional Research Service, July 31, 2026. https://www.congress.gov/crs_external_products/R/PDF/R49057/R49057.2.pdf.
Cybersecurity and Infrastructure Security Agency. "Information Technology Sector." Accessed August 18, 2026. https://www.cisa.gov/topics/critical-infrastructure-security-and-resilience/critical-infrastructure-sectors/information-technology-sector.
Darbro, Sadie. "How Rural Communities Are Shaping the AI Buildout." UChicago Sustainability Dialogue, University of Chicago, May 20, 2026. https://sustainabilitydialogue.uchicago.edu/news/how-rural-communities-are-shaping-the-ai-buildout/.
Electric Power Research Institute. Thermal Energy Storage and Load Shifting in Data Centers. Palo Alto, CA: EPRI, 2024.
Electric Reliability Council of Texas. Seasonal Assessment of Resource Adequacy (SARA). Austin: ERCOT, 2026.
European Commission. Commission Delegated Regulation (EU) 2024/1364 of 14 March 2024 on the First Phase of the Establishment of a Common Union Rating Scheme for Data Centres. Official Journal of the European Union, L 2024/1364, May 17, 2024. http://data.europa.eu/eli/reg_del/2024/1364/oj.
European Union.Explanatory Memorandum. Ares (2026)3247482. Brussels: European Commission, 2026. https://eur-lex.europa.eu/legal-content/EN/TXT/HTML/?uri=PI_COM:Ares(2026)3247482.
Executive Office of the President, Office of Management and Budget. Update to Data Center Optimization Initiative (DCOI). OMB Memorandum M-19-19. Washington, DC: Executive Office of the President, June 25, 2019. https://www.whitehouse.gov/wp-content/uploads/2019/06/M-19-19.pdf.
Foxhall, Emily. "Gina Hinojosa won the governor's race. What happens to Texas data centers now?" The Texas Tribune, November 4, 2026. https://www.texastribune.org/2026/11/04/data-center-texas-pause-gina-hinojosa-governor-policies/.
Germany. Gesetz zur Steigerung der Energieeffizienz in Deutschland (Energieeffizienzgesetz – EnEfG) [Energy Efficiency Act]. November 13, 2023. https://www.gesetze-im-internet.de/enefg/__11.html.
Gibson, Dunn & Crutcher LLP. "What Governor Abbott’s Data Center Audit Directives Mean for ERCOT Interconnections and TCEQ Environmental Permitting." Client Alert, August 14, 2026 (updated September 2026). https://www.gibsondunn.com/what-governor-abbotts-data-center-audit-directive-means-for-ercot-and-the-batch-zero-study-process/.
Information Technology Industry Council. "ITI to DOE: AI Infrastructure is Critical for U.S. Technological Leadership." News release, May 7, 2025. https://www.itic.org/news-events/news-releases/iti-to-doe-ai-infrastructure-is-critical-for-u-s-technological-leadership.
International Organization for Standardization. Data Centre Power Usage Effectiveness. 2021. https://www.iso.org/publication/PUB200301.html.
ISO. ISO/IEC 22123-3:2023 Information technology — Cloud computing Part 3: Reference architecture. Geneva: ISO, 2023.www.iso.org/standard/82759.html
Li, Pengfei, Jianyi Yang, Mohammad A. Islam, and Shaolei Ren. "Making AI Less 'Thirsty': Uncovering and Addressing the Secret Water Footprint of AI Models." arXiv, preprinted April 6, 2023. https://doi.org/10.48550/arXiv.2304.03271.
Milldam PR. "Milldam Public Relations Launches Data Center Community Benefit Agreement Development Service." April 2, 2026. https://milldampr.com/2026/04/02/illdam-public-relations-launches-data-center-community-benefit-agreement-development-service/.
Shehabi, Arman, Sarah Smith, Dale Sartor, Richard Brown, Magnus Herrlin, Jonathan Koomey, Eric Masanet, Nathaniel Horner, Inês Azevedo, and William Lintner. United States Data Center Energy Usage Report. LBNL-1005775. Berkeley, CA: Lawrence Berkeley National Laboratory, June 2016. https://eta.lbl.gov/publications/united-states-data-center-energy.
Siddik, Md Abu Bakar, Sheida Shehabi, and Lu Liu. "The Environmental Footprint of Data Centers in the United States." Environmental Research Letters 16, no. 6 (May 2021): 064017. https://doi.org/10.1088/1748-9326/abfba1.
Stanford Energy. "Stanford Water-Energy Nexus Framework." Stanford, CA: Stanford University, 2026. https://understand-energy.stanford.edu/news/understand-water-energy-nexus.
Texas Blockchain Council. "Feedback Post January 9, 2026 PUC Hearing Regarding PUCT Project No. 58481 (Large Load Interconnection Standards)." PUCT Project No. 58481, January 16, 2026. https://interchange.puc.texas.gov/Documents/58481_102_1575762.PDF.
Texas Comptroller of Public Accounts. "State Sales Tax Exemption for Qualifying Data Centers and Qualifying Large Data Center Projects." Accessed August 18, 2026. https://comptroller.texas.gov/taxes/data-centers/.
Texas Water Development Board. 2022 State Water Plan. Austin: TWDB, 2021. https://www.twdb.texas.gov/waterplanning/swp/2022/.
The Green Grid. "PUE: Powering Change Across the ICT Industry Infographic." September 1, 2015. https://archive.thegreengrid.org/en/resources/library-and-tools/217-PUE%3A-Powering-Change-Across-the-ICT-Industry-Infographic.
The Green Grid. Usage and Public Reporting Guidelines for The Green Grid’s Infrastructure Metrics (PUE/DCiE). Edited by Jon Haas and Jamie Froedge. White Paper #22. October 29, 2009. https://airatwork.com/wp-content/uploads/The-Green-Grid-White-Paper-22-PUE-DCiE-Usage-Guidelines1.pdf.
The Green Grid.. WUE: Water Usage Effectiveness: A Green Grid Data Center Sustainability Metric. White Paper #35. Beaverton, OR: The Green Grid, 2011. https://www.thegreengrid.org/system/files/store/WUE_v1.pdf.
Ziaei, Parsa, Oleksandr Husev, and Jacek Rabkowski. "Data Centers as a Driving Force for the Renewable Energy Sector." Energies 19, no. 1 (2026): 236. https://doi.org/10.3390/en19010236.